axis position monitoring system with gap sensor
Output alarm signal when displacement exceed set value
Alarm output is 2 points(HH,HI)
Length between gap sensor and monitor can be extended to several 10m with extension cable
Each setting can be changed easily
Power supply for sensor is built in monitor
Input signal | 1-5V |
Output pattern | Relay output(C contact point) |
Output point | 2 points(For HH/LL and HI/LO) |
Alarm type | Shared OR output for upper and lower limit alarm |
Comparative method | Judge magnitude relation between comparison setting value and display value by CPU(equal NG judgement) |
Contact point rating | AC250V/0.2A resistance load | DC30V/0.2A resistance load |
Mechanical life | More thah 10 million times |
Electrical life | More than 30 thousand times |
Comparative indication | Indicate by lights out of the front LED |
Comparative determination value | Upper(Lower) limit alarm : Independent set up at each contact point within 0.000~9999(-9999~0.000) |
ON delay | Independent set up at each contact point in the range of 0.0~99.9 sec. |
Indication mode | ME mode:Indicate displacement from standard point | GA mode:Indicate gap between sensor and target(GA lamp lighting) |
Indication go out | Light out indication at set time |
RESET | When RESET terminal is connected with COM terminal, comparative power and indication is capable of self-holding |
Test mode | It is capable of inputting the set indication, analog output and comparison output (lighting TE lamp) |
ZERO | Shift the whole for setting to zero |
Over range warning | Indicate OVER |
Power supply | AC85~250V 50/60Hz |